Home / Products / Temperature & Humidity Sensors / Integrated Temperature and Humidity Sensors
Skip to results list

Integrated Temperature and Humidity Sensors

( 3 items )

Filter

  • SX-THHD Series

    The SensorsX SX-THHD series measures relative humidity and temperature in industrial applications. It features an IP65-rated PC enclosure with a Ø15 mm probe. Two 4–20 mA two-wire current-loop outputs provide separate humidity and temperature signals. Wall, duct, remote-probe and DIN-rail mounting configurations are available. Standard and high-precision sensing options, an optional LCD, an optional Ex ia configuration and PC-based configuration support different installation requirements.

    • Measurements: relative humidity and temperature.
    • Humidity range: 0–100% RH.
    • Selectable temperature ranges: 0 to +50 °C; 0 to +100 °C; −40 to +60 °C; −10 to +50 °C; −20 to +80 °C; −40 to +80 °C; −40 to +125 °C.
    • Standard accuracy: ±2% RH at 20–80% RH; temperature ±0.3 °C.
    • High-precision accuracy: ±1% RH at 20–70% RH; temperature ±0.1 °C.
    • Temperature measurement error at 5–60 °C: ±0.3 °C standard / ±0.1 °C high precision.
    • Outputs: separate humidity and temperature 4–20 mA two-wire current loops.
    • Supply: 10–30 V DC per channel.
    • Fault output: ≤3.6 mA or ≥21.5 mA; default low-current alarm.
    • Current limit: ≤25 mA.
    • Temperature drift: 0.008% FS/°C.
    • Long-term stability: 0.05%/year or ≤0.1 °C/year.
    • Enclosure: PC; IP65; Ø15 mm probe.
    • Installation: wall / duct / remote / DIN-rail.
    • Operating environment: −40 to +85 °C; 0–95% RH, non-condensing.
    • Optional LCD ambient: −20 to +70 °C.
    • Storage: −40 to +85 °C; 20–80% RH.
    • Options: LCD display, Ex ia configuration and PC-based configuration.
    • Remote-mount versions require a separately ordered SX-THRD remote probe.
  • SX-THJD Series

    The SensorsX SX-THJD series measures relative humidity and temperature for industrial monitoring and control. Depending on the selected configuration, it also calculates dew point, absolute humidity and mixing ratio. The transmitter features an IP67-rated PC enclosure and is available in wall-mount, duct-mount and remote-probe versions. Versions with two 4–20 mA outputs provide galvanic isolation between the output channels, while an optional LCD displays two measured parameters simultaneously. DIP switches provide preset temperature-range selection and output-channel assignment, and a PC configuration tool supports parameter settings and one- or two-point temperature and humidity calibration.

    • Measurements: relative humidity and temperature; calculated dew point, absolute humidity and mixing ratio depend on configuration.
    • Humidity range: 0–100% RH; accuracy ±2% RH at 20–80% RH and 25 °C.
    • Integrated sensor temperature range: −40 to +125 °C; accuracy ±0.3 °C at 5–60 °C.
    • Temperature range options: 0 to +50 °C; 0 to +100 °C; −40 to +60 °C; −10 to +50 °C; −20 to +80 °C; −40 to +80 °C; −40 to +125 °C.
    • Pt100: Class A; Pt1000: Class B; DIN EN 60751.
    • Output options: 4–20 mA / passive Pt100 / passive Pt1000; select compatible sensing elements and outputs.
    • Current-output versions: two mutually isolated 4–20 mA two-wire channels; 10–30 V DC supply.
    • Common-positive or common-negative wiring electrically connects the output circuits.
    • Response time: 1 s.
    • Fault indication: ≤3.6 mA or ≥21.5 mA; default low alarm ≤3.6 mA.
    • Current limit: ≤25 mA.
    • Temperature drift: 0.008% FS/°C; long-term stability: 0.05%/year or ≤0.1 °C/year.
    • Enclosure: PC; IP67; Ø15 mm probe.
    • Installation: wall / duct / remote.
    • Ambient: −40 to +85 °C; LCD versions: −20 to +70 °C; 0–95% RH, non-condensing.
    • Storage: −40 to +85 °C; 20–80% RH.
    • Surge immunity: ±4,000 V; fast transient/burst: Level 4; optional isolation: 500 / 1,500 V AC.
    • DIP switches: preset temperature ranges and channel assignment; all ON enables PC configuration.
    • Remote configurations require a separately ordered SX-THRD probe.
  • SX-THKD Series

    The SensorsX SX-THKD series provides humidity-only, temperature-only and combined temperature and humidity measurement for industrial monitoring and control. Depending on configuration, it also calculates dew point, absolute humidity and mixing ratio. Its IP67 PC enclosure and stainless-steel probe support wall, duct and remote installation. Available outputs include 4–20 mA, 0–10 V, 0–5 V and passive Pt100/Pt1000, with galvanic isolation between dual current-output channels. The optional backlit LCD displays three values simultaneously, while DIP switches and PC configuration support range selection, channel assignment and one- or two-point calibration.

    • Measurements: humidity-only / temperature-only / combined temperature and humidity.
    • Humidity range: 0–100% RH; accuracy ±2% RH at 20–80% RH and 25 °C.
    • Integrated T/RH sensor: −40 to +120 °C; accuracy ±0.3 °C at 5–60 °C.
    • Selectable scaling: 0–50 / 0–100 / −40–60 / −10–50 / −20–80 / −40–80 / −40–125 °C; 125 °C requires a compatible sensing element.
    • Pt100: Class A; Pt1000: Class B; DIN EN 60751.
    • Outputs: 4–20 mA two-wire / 0–10 V / 0–5 V / passive Pt100 / Pt1000.
    • Dual current outputs: galvanically isolated; isolation voltage 1,500 V AC.
    • Supply: 10–30 V DC; response time: 1 s.
    • Voltage-output load: ≥10 kΩ.
    • Fault indication: ≤3.6 mA or ≥21.5 mA; disabled by default.
    • Display: optional backlit LCD, 128 × 64 pixels; three values simultaneously.
    • Enclosure: PC, IP67; stainless-steel probe.
    • Installation: wall / duct / remote.
    • Operating environment: −40 to +85 °C; 0–95% RH, non-condensing.
    • Storage: −40 to +85 °C; 20–80% RH.
    • Temperature drift: 0.008% FS/°C; stability: 0.05%/year or ≤0.1 °C/year.
    • Surge and fast transient/burst immunity: ±4,000 V.
    • Configuration: DIP switches and PC tool; one- or two-point temperature and humidity calibration.
    • Remote versions: specify the required probe and cable.