Product Overview
The SensorsX SX-ECFNA-300ALDGH current transducer uses fluxgate technology to measure DC, AC, pulsed and non-sinusoidal currents with galvanic isolation. It provides a secondary current proportional to the primary current at an output-to-input ratio of 1:2,000, with a nominal output of ±150 mA for a nominal DC input of ±300 A. The transducer requires a dual ±12 V to ±15 V supply and provides a frequency bandwidth of DC to 100 kHz (−3 dB). A green LED indicates normal operation.
Main Features
-
Accuracy: <0.05% at 25 °C.
-
Frequency bandwidth: DC–100 kHz (−3 dB).
-
Insulation withstand voltage: 5 kV AC (50 Hz, 1 min).
-
Response time: ≤1 µs.
-
Output current thermal drift: <10 ppm.
-
Green LED operating status indicator.
Product Application
Typical Applications
| Precision DC and AC current measurement |
Pulsed and non-sinusoidal current monitoring |
Galvanically isolated current measurement in industrial systems |
Technical Data
| Measurement |
| Measuring Principle |
Fluxgate; galvanically isolated DC, AC, pulsed and non-sinusoidal current measurement |
| Primary Nominal DC Current |
±300 A |
| Primary Nominal AC RMS Current |
212 A |
| Primary Measuring Range |
−440 to +440 A (±15 V supply, 10 Ω measuring resistance) |
| Output-to-Input Ratio |
1:2,000 |
| Power & Output |
| Supply Voltage |
Dual (bipolar) ±12 V to ±15 V (±5%) |
| Current Consumption |
20 mA + primary current / 2,000 |
| Secondary Nominal Output Current |
±150 mA |
| Measuring Resistance |
0–21 Ω at ±12 V; 0–40 Ω at ±15 V (at ±300 A maximum) |
| Secondary Coil Resistance |
48 Ω at 25 °C |
| Insulation Withstand Voltage |
5 kV AC, 50 Hz, 1 min |
| Mechanical & Connection |
| Aperture |
Ø20 mm |
| Electrical Connection |
4 terminals: positive supply, negative supply, current output and ground |
| Weight |
110 g |
| Performance |
| Accuracy |
<0.05% at 25 °C |
| Linearity |
±0.02% FS over 0 to ±300 A |
| Zero Offset Current |
<±10 µA at 25 °C |
| Zero Offset Thermal Drift |
<±10 µA at zero primary current, −40 to +85 °C |
| Output Current Thermal Drift |
<10 ppm at −40 to +85 °C |
| Response Time |
≤1 µs at 100 A/µs, 10%–90% |
| Frequency Bandwidth |
DC–100 kHz (−3 dB) |
| Tracked Current Rate of Change |
>100 A/µs |
| Environmental Conditions |
| Operating Temperature |
−40 to +85 °C |
| Storage Temperature |
−40 to +125 °C |
| Primary Conductor Temperature |
Cable or busbar temperature must not exceed 100 °C |